HIKVision Conventional Heat Detector (with base)
The Hikvision HF-CH1 is a conventional heat detector designed for fire alarm systems. It uses a high-reliability thermistor sensor with intelligent temperature compensation to detect abnormal heat conditions. With a two-wire connection, 24VDC operation, and suitability for humid or dusty environments, it provides reliable fire detection where smoke detectors may not be suitable.
₨875 inc. Vat
Credit by Rogers Finance: ₨1,006
Apply with Rogers code - RTDL01
The Hikvision HF-CH1 is a conventional fixed-temperature/rate-of-rise heat detector designed for use with Hikvision conventional fire alarm systems. It detects fire conditions by monitoring temperature changes through an advanced thermistor sensing element, providing stable and accurate heat detection while reducing false alarms.
Unlike smoke detectors, the HF-CH1 is ideal for locations where smoke detection may be unsuitable due to dust, humidity, steam, or environmental conditions. It is commonly used in kitchens, warehouses, workshops, parking areas, industrial facilities, and other areas requiring dependable heat-based fire detection.
The detector features a 360° visible red alarm indicator, two-wire polarity connection, low standby current consumption, and a compact ceiling-mounted design. Its intelligent temperature compensation algorithm improves detection reliability across different operating environments.
Key Specifications
- Model: HF-CH1
- Device Type: Conventional Heat Detector
- Detection Technology: Thermistor-based heat sensing
- Detection Type: Heat / Temperature detection
- System Type: Conventional fire alarm system
- Operating Voltage: 24VDC (18–28VDC)
- Wiring: Two-wire, polarity sensitive
- Monitor Current: ≤300 μA
- Alarm Current: ≤15 mA
- Indicator: 1 × Red LED alarm indicator
- Sensor Type: High-reliability thermistor
- Temperature Compensation: Intelligent temperature compensation algorithm
- Installation Type: Ceiling mount
- Material: ABS housing
- Dimensions: Ø100 mm × 49 mm (with base)
- Weight: Approx. 92 g
- Cable Requirement: RVS 2 × 1.5 mm² flame-retardant cable
- Maximum Wiring Distance: Up to 500 m
- Application Environment: Commercial and industrial areas, humid/dusty locations where smoke detectors are unsuitable.
Typical Applications
- Warehouses
- Workshops
- Kitchens
- Parking areas
- Industrial buildings
- Boiler rooms
- Commercial premises requiring heat-based fire detection